3-2 I/O Communication
3-19
3
Communicating with the SK-1000 Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (SK-1000) -
Rewriting a setting value of a sensor amplifier
Available setting values: HI setting value (Bank0), Low setting value (Bank0)
Device assignments: "Rewrite setting value" (page 3-13)
The setting value to be rewritten is the values listed above. In case of
rewriting the setting value of a BANK number other than the values
listed above, see "Reading/Writing Settings or Status of a Sensor
Amplifier" (page 3-23).
When rewriting any setting or parameter other than listed above, use the
procedure described in "Reading/Writing Settings or Status of a Sensor
Amplifier" (page 3-23).
This example changes the HI setting value of ID01.
It assumes that the operating mode assigned to the device is 3-output mode.
(1)Write the new setting value in the "setting-value rewrite data." For details of
writable ranges, see "Command parameter list for SK-1000 series" (page 3-
28).
(2)Execute the "request to rewrite setting value" command (0 -> 1).
(3)After the setting v alue is rewritten, the "setting value rewrite complete" signal flips
from 0 to 1.
(4)If an error occurs during "setting value rewriting" on the sensor amplifier, the
"setting value rewrite error" signal flips from 0 to 1. (The output is an OR sum of
settings.) Check the value ent
ered in the "setting-value rewrite data.
"
(5)When the "request to rewrite setting value" command is set to 0, the "setting value
rewrite complete" and "setting value rewrite error" parameters flip to 0.
PLC
(1)
Setting-value rewrite data
1234h
OUT area [m+4]
(2) (5)
Request to rewrite setting value
OUT area [m+3] BIT 0
(3)
Setting-value rewrite complete
IN area [n+8] BIT 0
(4)
Setting- value rewrite error
IN area [n+7] BIT 0
Sensor amplifier
Setting-value 1234h
1
0
1
0
1
0