3-4 Message Communication
3-41
3
Communicating with the SK-1000 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
Group3
0369H
(873)
System
parameter
settings
*7
Set up system parameter.
To reflect the setting, you need to send
"System parameter set request" (0306H (774))
operation command after writing the setting.
Use 0338H (824) to check the system
parameter with which the sensor amplifier is
operating.
bit 0:
0: NPN
1: PNP
bits 1, 2 and 3 (For main unit only. Fixed to 000
for expansion unit)
000: Analog output OFF
001: 0 to 5V
010: -5 to 5V
011: 1 to 5V
100: 4 to 20mA
R/W DINT
036AH
(874) to
037FH
(895)
(Reserved for system)
Group4
0380H
(896)
Group4 Entry
count
Indicates the No. of Group 4 entries.
Parameter range: 26
RDINT
0381H
(897)
(Reserved for system)
0382H
(898)
Range setting
Set up measurement range.
Parameter range: 0 to 2 (initial value: 0)
0: NEAR
1: FAR
2: Ib
R/W DINT
0383H
(899) to
0384H
(900)
(Reserved for system)
0385H
(901)
Averaging
Set up averaging/diff. count filter/high-pass
filter.
Parameter range: 0 to 8 (initial value: 5)
0: 1 time
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 64 times
6: 256 times
7: 1024 times
8: 4096 times
9: 16384 times
R/W DINT
0386H
(902)
Output mode
Set up output mode.
Parameter range: 0 to 1 (initial value: 0)
0: N.O.
1: N.C.
R/W DINT
0387H
(903)
(Reserved for system)
0388H
(904)
Hold function
setting
Set up hold function.
Parameter range: 0 to 5 (initial value: 0)
0:Sample hold
1:Peak hold
2:Bottom hold
3:Absolute value hold
4:Auto peak hold
5:Auto bottom hold
6:Auto absolute value hold
R/W DINT
Class
Attribute
ID
Name Description
Attribute
Data
Typ e