KEYENCE CORPORATION. Vision System Division
‐ 20 ‐ www.keyence.com
0 10 1
1 0 1 1 1
10
0 0 0
10
1
0 0 1 1 0 01 0 1
0 1 1 1
Execute No. to rewrite to (0 to 99)
I/O terminal control (EXW: Write execute condition)
Sets the Currently Valid Execute No. to the specified execute No.
EXW command: Write execute condition
Sample EXW command execution procedure: Writing 7 in Execute No.
1. Turn IN8, IN9 and IN10 ON, and enter "7" in binary into CMD_PARAM (IN7 to 0).
2. Set CST (IN12) to ON.
3. CMD_READY (OUT3) turns OFF, and the Currently Valid Execute No. changes to the specified No.
4. When the Execute No. has been written, ACK (OUT0) turns ON for the specified amount of time (set in "Global" >
"Communications & I/O" > "External Terminal"). When ACK turns off, CMD_READY (OUT3) turns ON.
* If the command execution fails, NACK (OUT1) turns on for the specified amount of time instead of ACK. Ensure that the
wiring and CMD_CODE/CMD_PARAM specifications are correct.
1: ON (short circuit), 0: OFF (open)
1: ON (short circuit), 0: OFF (open)
1: ON (short circuit), 0: OFF (open)