Keyence Visual KV Series Bedienungsanleitung Seite 379

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 444
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 378
9.4 Programming
KV-10/80 Series Only
KV-300
KV-10/80
Chapter 9 KV-AD4/DA4 Analog I/O Unit
1-355
1
9
How to calculate digital data when outputting analog current
Digital data = (output current (
µA) ÷ resolution (4 µA)) - offset value (1000)
Example
When outputting 18 mA
(18000 (µA) ÷ 4 (µA)) - 1000 = 3500
Write "3500" to data memory for D/A conversion.
Next, turn ON the special utility relay for D/A conversion.
Resolution
"Resolution" refers to the minimum analog output value by which digital data can be
changed. For example, 5 mV is the resolution of output range -10 to +10 V. This
indicates that the analog output changes by 5 mV when the value of the digital data
changes by 1.
Digital data content
The KV-DA4 voltage and current output characteristics are as follows.
For example, the digital data for outputting +5 V is 3000.
Digital
data
+1000
+2000
+3000
+4000
+10
-8
-6
-4
-2
0
+2
+4
+6
+8
Range: ±10 V
-10
Voltage
(V)
Voltage output characteristics
Digital
data
+1000
+2000
+3000
+4000
0
2
6
8
10
12
14
16
18
Current
(mA)
20
4
Range: 4 to 20 mA
Current output characteristics
KVHKA Chap 09.p65 08.3.11, 11:20 AM355