Appendices
2-163
1
Appendices
Appendix B Instruction List
This appendix includes a list of instructions and an outline of their processes. For
details, refer to Chapter 2, "Instructions" on page 3-33.
B-1 Basic instructions
Instruction name Mnemonic Outline of process
Load LD Connects N.O. contact to bus.
Load Bar LDB Connects N.C. contact to bus.
Out OUT Outputs ON/OFF status of input to relay coil.
Out Bar OUB Outputs inverted ON/OFF status of input to relay coil.
And AND Connects N.O. contact in series.
And Bar ANB Connects N.C. contact in series.
Or OR Connects N.O. contact in parallel.
Or Bar ORB Connects N.C. contact in parallel.
And Load ANL Connects in series the blocks made of one or more
contacts.
Or Load ORL Connects in parallel the blocks made of one or more
contacts.
Set SET Turns ON specified relay forcibly, and enables it to
remain ON.
Reset RES Turns OFF specified relay forcibly.
Timer TMR Sets an on-delay timer that counts down in 0.1 s
increments.
High-Speed Timer TMH Sets an on-delay timer that counts down in 0.01 s
increments.
High-Speed 1-ms TMS Sets an on-delay timer that counts down in 0.001 s
Timer increments.
Counter C Sets an up counter.
Up-Down Counter UDC Sets an up-down counter.
Differentiate Up DIFU Detects rising edge of input signal and turns ON
specified relay for first scan time only.
Differentiate Down DIFD Detects falling edge of input signal and turns ON
specified relay for first scan time only.
Keep KEEP Turns ON specified relay when SET input relay turns
ON, and enables this relay to remain ON. Turns OFF
specified relay when RESET input relay turns ON.
Shift SFT Sets a shift register.
High Speed HSP Shortens time constant of specified input relay to be
ready for high speed.
Master Control MC Selects ON/OFF status of relays, timers or counters
set before MCR instruction.
Master Control MCR Ends the execution of MC instruction.
Reset
Memory Switch MEMSW Sets memory switches.
No Operation NOP Performs no operation.
End END Indicates end of each routine in the program.
End Hi ENDH Indicates end of entire program.
KVSKA Appendix.P65 08.3.11, 11:26 AM163