3-2 Device Maps
3-7
3
Communicating with the FD-S series
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
Number [n] denotes the first data memory number assigned to the DL-CL1.
*1 See "Entering an External Input into a Sensor Amplifier" (page 3-17).
*2 See "Reading Current Values (Instantaneous Flow Rate) from Sensor Amplifiers" (page 3-18).
*3 See "Reading/Writing Settings or Status of a Sensor Amplifier" (page 3-21).
See "Issuing a Motion Command to a Sensor Amplifier" (page 3-20).
*4 See "Error information list" (page 3-8).
*5 See "Command response list" (page 3-8).
*6
See "Command Parameter List" (page 3-24).
Operating
mode
Device no.
(HEX)
Name
Communication
method
Description Reading rang e
Small-memory mode 2
Monitor mode 1
RWr[n] + 04
Integration
reset input
response
*1
Stores the integration reset input response of
the sensor amplifi er.
The response is output by assigning sensor
amplifi ers (ID 01 to ID 04) to bits 0 - 3.
0: Input OFF
1: Input ON
RWr[n] + 05
Flow rate
hold reset
input
response
*1
Stores the fl ow rate hold reset input response
of the sensor amplifi er.
The response is output by assigning sensor
amplifi ers (ID 01 to ID 04) to bits 0 - 3.
0: Input OFF
1: Input ON
RWr[n] + 06
Zero
adjustment
input
response
*1
Stores the zero adjustment input response of
the sensor amplifi er. The response is output
by assigning sensor amplifi ers (ID 01 to ID
04) to bits 0 - 3.
0: Input OFF
1: Input ON
RWr[n] + 07
Current value
property
*2
Used for reading the instantaneous fl ow rate
value.
This property is output by assigning IDs (ID
01 to ID 04) to bits 0 - 3.
The output occurs when the instantaneous
ow rate value read from the sensor amplifi er
is nonnumeric: "over" or "invalid."
0: Normal current
value
1: "over" or "invalid
(-----)"
RWr[n]
+08 to 09
(INT32)
Current
value: box 1
*2
Used for reading the instantaneous fl ow rate
value. The instantaneous ow rate value of the
sensor amplifi er of the ID number specifi ed
page number (RWw[n] + 08) is output.
Data type:
INT3
2 (LITTLE)
Page 0: ID 01
Page 1: ID 04
RWr[n]
+0A to 0B
(INT32)
Current
value: box 2
*2
Used for reading the instantaneous fl ow rate
value.The instantaneous fl ow rate value of the
sensor amplifi er of the ID number specifi ed
page number (RWw[n] + 08) is output.
Data type: INT32 (LITTLE)
Page 0: ID 02
Page 1: (Not used)
RWr[n]
+0C to 0D
(INT32)
Current
value: box 3
*2
Used for reading the instantaneous fl ow rate
value.
The instantaneous fl ow rate value of the
sensor amplifi er of the ID number specifi ed
page number (RWw[n] + 08) is output.
Data type: INT32 (LITTLE)
Page 0: ID 03
Page 1: (Not used)
RWr[n] + 0E
Temperature
hold reset
input
response
*1
Stores the temperature hold reset input
response of the sensor amplifi er.
The response is output by assigning sensor
amplifi ers (ID 01 to ID 04) to bits 0 - 3.
0: Input OFF
1: Input ON
RWr[n] + 0F (Not used) - -- --