5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
5-7
5
Appendix
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -
2
Add "ETHERNET-MODULE (Generic Ethernet Module)".
3
Change the settings as required.
Name
Choose a name. The following tags are generated based on the name set
here, and are used as the data exchanged with cyclic communication.
• (Name): I Data received from DL-EP1
• (Name): O Data sent to DL-EP1
• (Name): C Not used.
Comm Format
Designate [Data INT].
IP Address
Designate the DL-EP1's IP address.
Input (DL-EP1 send data size)
• Instance number: 100 (decimal)
• Data size: Value up to 84
Output (DL-EP1 receive data size)
• Instance number 101 (decimal)
• Data size: Value up to 5
Configuration
• Instance number: 1 (decimal)
• Data size: 0
Seitenansicht 86