2.4 Instruction Details
1
2
3-97
Chapter 2 Instructions
Description
W-ON
When input relay 0000 is ON, output operand 1000 turns ON as soon as the
contact of input operand 0001 turns ON.
W-OFF
When input relay 0002 is ON, output operand 1001 turns ON as soon as the
contact of input operand 0003 turns OFF.
Note: Output operand relay Nos. for W-ON/W-OFF instructions cannot be dupli-
cated in a program.
Operands
* Note that of I/O Nos. 7000 to 9915, those that are not assigned to expansion or
remote I/O unit ports can be used for internal utility relays.
Key operation
0002 0003
1001
0002
0003
OFF
1001
1001
0000 0001
1000
0000
0001
ON
1000
1000
Same
operation
Input operand
Output operand
W-ON
F
W-OFF
Li
First operand
(nnnn)
Second operand
(mmmm)
ENT
R-SRCH
Same
operation
Input operand
Output operand
W-ON / W-OFF
Visual KV KV-300 KV-10/16 KV-24/40/80
nnnn: nnnn: nnnn: nnnn:
0000 to 17915 0000 to 0009 0000 to 2915 0000 to 6915
T000 to T249 0500 to 17915 T000 to T063 T000 to T119
C000 to C249 T000 to T249 C000 to C063 C000 to C119
CTC0 to CTC3 C000 to C249 CTC0 to CTC3 CTC0 to CTC3
mmmm: CTC0 to CTC3 mmmm: mmmm:
1000 to 1915 mmmm: 1000 to 1915 1000 to 1915
3000 to 9915 1000 to 1915 3000 to 6915
3000 to 6915
*7000 to 9915
KVNKA Chap 02_4bP.p65 08.3.11, 11:59 AM97