Seitenansicht 129
2.4 Instruction Details
3-106
2
Chapter 2 Instructions
Example
1) When transition condition relay 0000 is ON, transfers execution to STG1001.
2) 0500 turns ON. When transition condition relay 0001 is ON, transfers execution
to STG1002.
3) 0501 turns ON. When transition condition relay 0002 is ON, transfers execution
to STG1001 and repeats the process above.
When transition condition relay 0003 turns ON, transfers execution to STG1000
and 1003.
4) 0502 turns ON. The process finishes when transition condition relay 0004 turns
ON.
Coding
STG: Stage
JMP: Jump
ENDS: End Stage
Executes instructions in STG block when operand relay is ON.
When transition condition relay is ON, turns OFF relay of current
stage and transfers execution to stage specified by operand.
When transition condition relay is ON, turns OFF relay
of current stage.
ENDS
nnnn
JMP
nnnn
STG
LDB
4
LDB
4
LDB
4
SET
1
SET
1
ANL
2
FUN
FUN
FUN
Initial setting
2008
0000
0500
1001
JMP
1000
STG
0001
1002
JMP
1001
STG
0502
0004
ENDS
1003
STG
0501
0002
1001
JMP
1002
STG
0003
1000
JMP
1003
JMP
1000
SET
1)
2)
3)
4)
Line No. Instruction Operand Line No. Instruction Operand
0000 LD 2008 0013 MPS
0001 SET 1000 0014 AND 0002
0002 STG 1000 0015 JMP 1001
0003 AND 0000 0016 MPP
0004 JMP 1001 0017 AND 0003
0005 STG 1001 0018 JMP 1000
0006 OUT 0500 0019 JMP 1003
0007 CON 0020 STG 1003
0008 AND 0001 0021 OUT 0502
0009 JMP 1002 0022 CON
0010 STG 1002 0023 AND 0004
0011 OUT 0501 0024 ENDS
0012 CON
:
:
: