8.2 Details
3-339
1
8
Chapter 8 Programming Examples
2008
2002
CTH1
0005
RES
CTH1
SET
2203
SET
2813
#60000
CTC2
CTC2
RES
0502
RES
CTC2
T001
0502
#00030
T001
High-speed counter current value clear
Counts pulses at input relay 0005. When the count value reaches setting value
60000, clears the current value of high speed counter CTH1 and turns ON output
relay 0502 for 3 s.
Ladder diagram Coding
Input of phase differential signal
Inputs phase differential signals to input relays 0004 and 0006 and counts pulses at
CTH0.
Writes the count value into DM0000.
When high speed counter CTH0 reaches 60000, clears the current value of CTH0,
sets output relay 0500, and stops fetching count value to CTH0.
Sets 0008 as external reset.
Ladder diagram
Note: Initial settings for special utility relays
Sets input time constant of input relays 0000 to 0009 to 10 µs when 2813 turns
ON.
Clears the current value of CTH0 when 2103 turns ON and CTC0 is ON.
Sets CTH0 in the X 2 mode when 2113 is ON and 2114 is OFF.
Enables external reset (input relay 0008) when 2115 turns ON.
Line No. Instruction Operand
0000 LD 2008
0001 SET 2813
0002 CON
0003 SET 2203
0004 CON
0005 RES CTH1
0006 LD 2002
0007 CTH1 0005
0008 CTC2 #60000
0009 LD CTC2
0010 OUT 0502
0011 CON
0012 TMR 001 #00030
0013 CON
0015 AND T001
0016 RES CTC2
0017 CON
0018 RES 0502
2008
RES
CTH0
SET
2115
0500
RES
2114
SET
2113
SET
2103
SET
2813
EI
CTH0
00004
#60000
CTC0
2002
STA
DM0000
LDA
CTH0
END
INT
CTC0
2002
SET
0500
RETI
ENDH
Initial settings
*Note
KVNKA Chap 08.p65 08.3.11, 0:12 PM339